Hi,
First, check the range configured for your device, furthermore that the FP-AI-110 is channels independantly configurable. Be sure that you allow a little excess in the range (i.e. 3.5mA instead of 4mA, and 21mA instead of 20mA).
And check also that you don't have unwired inputs which can cause "out of range" error cause of external noise.
If that still doesn't work, could you inform about the interface module used, and about the wiring of your input?
I hope this Helps.
Regards,
Olivier L.
Application Engineer
Olivier L. | Certified LabVIEW Developer