Dear Steven,
We have confirmed than almost all those modules are miscalibrated. We have measured -4,xx and -2,xx Celsius degrees like offsetts in two modules. By the same way, it is very important to know the exact length of cabling from PT100 sensor to FP-PT100 module, in order of adjust the final measured values. Question: Is it possible to calibrate the FP-PT100 2 wires modules in our laboratory?
Best Regards,
Eduardo