08-07-2012 09:55 AM
I am using a cDaq 9178 chassis with one NI-9205 and 6 NI-9481. When I try to use the DAQ Assistant I can communicate with the 9205 but it locks LabView up when I try to create a digital output for any of the 9481's. Any idea what is causing this problem?
08-07-2012 10:08 AM
my best guess would be a driver incompatability. Are you using the latest DAQmx and RIO?
08-07-2012 10:23 AM
No, just DAQmx.
08-07-2012 11:33 AM
OK, Which version of DAQmx are you using? (You can find it in MAX under Software)
08-07-2012 11:36 AM
Version 5.1
08-07-2012 01:58 PM
The latest is 9.5.1. you can download it here DAQmx 5.1 predates the hardware you are using so of course it does not have support for that device.
Im just a bit concerned that your system is that out of date. Check the compatability matrix for the LabVIEW version you are using.