You are right, this is typical of a race condition with local variables. The local is read before the control is updated.
Do not use locals. Go to the Data communication subpalette (LV 😎 or Advanced subpalette (LV 7 and before) and have a look at the synchronize functions. Study the corresponding examples shipped with LabVIEW.
Alternatively, consider using the event structure in a single loop.