LabVIEW

cancel
Showing results for 
Search instead for 
Did you mean: 

what is the maximum rate we can achieve using 9403 in digital switching

what is the maximum rate we can achieve using 9403 in digital switching?

 i am using 9102 chassi and 9012 controller.

 i am trying to program the 9403 as the output port and i am using it for switch on one of my devices.

                      minimum pulse width should be =1micro second

 

0 Kudos
Message 1 of 2
(2,263 Views)

Have you looked at the specifications in the user manual for the 9403?

http://www.ni.com/pdf/manuals/374069e.pdf

 

Looks likethe update rate for the 9403 using a cRIO 9102 chassis is 7microsec.  I don't think you can get 1 microsec pulse width using the 9403, maybe try the 9401 or other high-speed module.

 

Dan

0 Kudos
Message 2 of 2
(2,256 Views)