08-09-2009 01:45 AM
Testing....
Having the following error on GE Series 90 (Ethernet) object.
"Error connecting: Unknown port name specified"
IP address is correct and pingable. Identical process runs fine on a W2k3 server. Firewall off.
This may also be an issue with Server 2008 prior to R2 ?
Can anyone else confirm/reproduce please?
Ed
08-24-2009 01:22 PM
what is the cpu ?
ge series 90 driver work only with cpu 364
with cup 37_ is necessary to use ge versamax driver (but is limited to 2k register)