I use NI cDAQ 9174 and NI 9203. I have already installed the driver for the NI cDAQ 9174 which is NI-DAQmx 9.8.0. I can see the device when I open NI MAX. However, when I open LabView 2015, I can't find DAQ Assistant in the Function Palette. I noticed that on the chassis the "ACTIVE" indicator light is not on whereas two other light "POWER" and "READY" is on. I did look at in the NI forums but I can't find the solution.
Any suggestion, please help !!!!
Thanks!
Solved! Go to Solution.
10-28-2016
06:38 AM
- last edited on
11-26-2024
01:41 PM
by
Content Cleaner
DAQmx 9.8 is not compatible with LabVIEW 2015. You need to use at least DAQmx 15.0. See here for more details: NI-DAQmx and LabVIEW Compatibility
10-28-2016 10:05 AM
Thanks crossrulz! It works fine now.