Mike -
To recap, you are using a custom step type to define that step instances of the step type use the Sequence Call adapter.
To change the default tracing value for the step type and any steps in sequence files that are currently loaded in the sequence editor, you can:
1) Turn on hidden properties in Station Options.
2) View the subproperties of the type.
3) Find the "TS.SData.Trace property" in the type.
4) Change the value from "Don't Change" to "Off" and select the "Apply Value to All Loaded Instances of the Type".
This will update the type's default value and change any instance's value for this property.
By the way, why are you using a custom step type instead of using NI's Sequence Call step type?
Are you just doing this so that the insert list has a list of the "library steps" that your users would like to insert?
Scott Richardson (NI)
Scott Richardson
https://testeract.com