Hi I am having issues with my cRIO-9063 booting into "Install Mode".

 

I have two cRIO-9063 running the same vi.  The cRIO has had the ni-rt.ini file modified to run my vi form.vi on start up. Both systems have been running fine since august.  This includes a number of restarts.  Then, this week, the power was cycled for cRIO number two.

 

  When the cRIO booted back on, it is now in "Install Mode".  I still have access to the web interface, and I can boot it into Safe Mode.  However, I have no idea how to get it out of install mode.

 

  Also, is there some mistake I made that lead to the cRIO being stuck in install mode?

 

Thanks for any help, and please let me know if you need more information

0 Kudos
Message 1 of 2
(3,130 Views)
Solution
Accepted by topic author samtbacon

To answer my own question.

 

My issue was I had used up the memory on the cRIO in install mode.  The disk space had gone to zero, and was booting into install mode as a result.

 

I enabled SSH shell script, remoted in, deleted the impeding logs, and cRIO works fine.

 

In my code, I had an auto error log function for certain errors.  cRIO one, had few errors.  cRIO two, had a lot more.  As a result, cRIO number two filled up its disk first.  