Greetings Robert,
The NI 6503 is not a correlated I/O card, meaning that digital measurements or digital generations are not performed on a clock. It is only a static digital input/output device. The supported timings for this device are On Demand or Handshake modes. Each time a DAQmx Read or DAQmx Write is called, the read or write, respectively, will be perfomed. There is no buffering or continuous acquisition of data with this device.
Hope that helps explain the error. Please let me know if you have any additional questions...
Regards,
Nicholas B, National Instruments