No. The sensor output is still 12 V and its internal resistance is less than the 2200 ohms so you would still give overvoltage to the DAQ input. To do something like that you should probably use a comparator with w 5 V output. Then you could use the counter as you have been wanting to do.

 

Lynn

0 Kudos
Message 31 of 37
(1,339 Views)

This time i run the cod in attachment and after a while this error comes;

error.png

 

What can be the reason?

 

 

0 Kudos
Message 32 of 37
(1,324 Views)

This time i used voltage regulator as seen in attachment

 

0 Kudos
Message 33 of 37
(1,319 Views)

That will not work.  Find someone who understands electronics and ask them to build a suitable signal conditioning circuit for you.

 

Lynn

0 Kudos
Message 34 of 37
(1,310 Views)
With all of your random circuits and programming attempts, I would not be a bit surprised if you haven't already destroyed DAQ device. DISCONNECT out and do not connect until you have a functional signal conditioning setup that you verify with an oscilloscope. Then, if the code does not work, you can consider getting a new card.
Message 35 of 37
(1,297 Views)

Is that the right block diagram for counter terminal?Because when i run it seems like it is running forever and push the stop button the view is not changing.

Please help

Regards

0 Kudos
Message 36 of 37
(1,264 Views)

Sgirgin,

 

That block diagram looks fine for a Counter Input task, but like was said before, there's a good possibility that your DAQ card may be damaged at this point.

 

Have you verified your signal using an oscilloscope?

Ty Prather
Technical Marketing Specialist
National Instruments
0 Kudos
Message 37 of 37