Hello Phil,
I have tried to answer your questions as best I can below:
#1. Yes, the SCB-68 will only accept voltage inputs. However, it has sockets for precision resistors that can be used for current measurements. You mentioned that you had viewed the documentation online, but I am not sure which documentation you were referring to. If you have not seen that document, I would recommend that you check it out. If you have seen that document, let me know which part is not clear and I will do my best to explain. Additionally, this method is also described on page 5-16 of the SCB-68 68-Pin Shielded Connector Block User Manual (page 61 of the PDF).
#2. & #3. When accessory power is enabled, I/O pin 8 is fused and is intended to be connected to +5V. This enables the CJC on the SCB-68 for use with your external thermocouple. There is more information about how to configure this option on page 4-2 of the SCB-68 68-Pin Shielded Connector Block User Manual (page 44 of the PDF). This should not have an affect on the current measurement as described in #1. So, I guess the answers to these questions are: #2. To my knowledge, it should not matter as long as you are not using ai0. and #3. Yes, if you are planning on using the onboard CJC with your thermocouple.
#4. While the SCB-68 does have some onboard signal conditioning options built in, it is still basically a connector block. It cannot provide excitation current for external devices.
#5. I can't help but ask, is there a story behind this? "Wang" is definitely a long stretch from Phil.
I hope this information is helpful. Please let me know if there's anything else I can do to help.
03-08-2007 01:55 PM
We have an Omega HX15 humidity/temp probe supplying it's own current loop,
and it's connected to terminal block as "Differential non-referenced".
New task configured in Measurement & Automation "Data Neighborhood".
My setup is SCB-68 connected to PCI-6250 and configured:
Ai0 > Omega RTD 1K platinum probe analog input into channel 0 as "RTD"
- looks like it's taking test samples, but I am very much a beginner in SW
Ai1 > Omega HX15 Humidity probe analag input channel 1
- no reading of samples when self test is run
I have tried setting switches on SCB-68 to temperature enabled,
with accessory power on and vice-versa. I will have to jumper
the internal ic temp sensor for my setup will I not?
I have a problem with the math, but could be I have to put a resistor
across the differential pairs and setup Ai0/1 to take 1-5 volt reading?
IF PCI-6250 accepts current readings, please help calculate loop resistance:
Rmax = (24 volt supply - 7 volts)/.02 amps
850 ohms? I have 22 awg wire on loop, should that total 865 ohms Rmax?
When I enter current max "20m" for 20 mA and 865 ohms I get error message,
and it is expecting a different ohm total. Math is my weakest conceptual subject.
Should I have to return the Omega probe and seek a probe that does not
supply it's own current loop. That seems like the answer to this problem.
Regards,
Phil Johnson
03-11-2007 10:49 PM