Crio 9075 driver for 9870 (running the scan engine)

Solved!
Go to solution

Hi,

 

I want to use a 9870 (rs232, 4 ports serial interface) on a 9075 CRIO.  I also want my labview project to be running on the scan engine.(running on Labview 2010 SP1)

I used this configuration several times using a 9073 CRIO very easely.

 

But now i can't find the correct set of driver for the CRIO 9075 to make this work.

 

Anyone can help me?

 

 

 

0 Kudos
Message 1 of 4
(6,457 Views)

Hello slvn,

 

I think that you may need to update your drivers further. Using FPGA/Real-time on the NI-9075 you will need. LabVIEW 2011 LabVIEW RT 2011 and NI-RIO 4.0. What is the latest version of LabVIEW that you have access to?

0 Kudos
Message 2 of 4
(6,431 Views)

Labview 2010 SP1 is the latest version i have access to.

Am i stuck?

 

0 Kudos
Message 3 of 4
(6,425 Views)
Solution
Accepted by topic author slvn

The NI 9075 cRIO needs a minimum of LabVIEW 2011 to be compatible if you are using the Real-Time module. I'm afraid to say that you are stuck until you can get a later version of LabVIEW. I believe this is the reason that you are able to get your set up to work on the 9073 but not the 9075. 

Ryan
Applications Engineer
National Instruments