08-14-2017 02:54 PM
Hi,
Regarding the PXI-2584 specs. The sheet says the max channel-ground voltage is 600V ACpk. Would I be able to run 480 Vrms through the channel safely?
Thanks.
Solved! Go to Solution.
08-15-2017 04:01 AM
Assuming a pure sine wave, Vpk=Vrms × √2 = 480 × √2 = 679. So I would say you should not run that through this switch.