05-14-2013 04:55 AM
Hi Forum,
I am using LabVIEW 2012 and NIVS 2012. Currently, i am designing my first system definition. I need to scale one of Analog Input from PXIe-6363 to some factor by using "Add Scale>>Polynomial Scale". I have always get error for any scale function i added.
It is an undefined error.
Someone has an idea?
Regards,
Rajamodol
Solved! Go to Solution.
05-14-2013 10:11 AM
I'm not sure why you see no error explination. On my computer it says
Possible reason(s):
NI VeriStand: A polynomial scale mapped to a channel(s) does not have reverse coefficients defined. Remove the mapping or update the scale to contain reverse coefficients, and then try to deploy the system definition again.
05-17-2013 06:20 AM
Hi StephenB,
Yes, i only need to go to reverse coefficent and Generate it. Problem solved.
Thanks,
Rajamodol