VeriStand

cancel
Showing results for 
Search instead for 
Did you mean: 

Scaling: Error -307888

Solved!
Go to solution

Hi Forum,

 

I am using LabVIEW 2012 and NIVS 2012. Currently, i am designing my first system definition. I need to scale one of Analog Input from PXIe-6363 to some factor by using "Add Scale>>Polynomial Scale". I have always get error for any scale function i added.

 

It is an undefined error.

 

NIVS2012 Error-307888.png

 

 

Someone has an idea?

 

Regards,

 

Rajamodol

 

 

 

 

0 Kudos
Message 1 of 3
(5,860 Views)
Solution
Accepted by topic author rajamodol

I'm not sure why you see no error explination. On my computer it says

 

Possible reason(s):

NI VeriStand:  A polynomial scale mapped to a channel(s) does not have reverse coefficients defined. Remove the mapping or update the scale to contain reverse coefficients, and then try to deploy the system definition again.

Stephen B
Message 2 of 3
(5,850 Views)

Hi StephenB,

 

Yes, i only need to go to reverse coefficent and Generate it. Problem solved.

 

Thanks,

 

Rajamodol

0 Kudos
Message 3 of 3
(5,811 Views)